135-2. DeSiGN reQUireMeNtS                                                                        DRAFT

         Building Facade Elements


         e.  Arcade Openings. Openings shall not be flush       B.  Non-Storefronts. The following regulations apply to
            with interior arcade ceiling and may be arched or      all non-storefront facades along sloping streets:
            straight.                                             1.  Grade transitions at the building along the
         F.  Horizontal Facade Division. A horizontal shadow          sidewalk shall be designed to minimize blank
            line shall define the ground story facade from the        walls. Multiple front entrances along the street
            upper stories.                                            activate each segment of building section at each
         G. Visible Basement. A visible basement is not               grade.
            permitted.                                            2.  The interior floor level shall step to match the
         H. exception. A type 1 design exception may be               changes in exterior grade within a 3-foot range.
            submitted for approval of an alternate arcade             With a type 1 design exception, deeper transition
            design.                                                   zones between the sidewalk and building facade
                                                                      of porches, terraces, and landscape areas may
         2.3.13  GrOUND StOrY At SlOPiNG FAcADeS                      be used assist with grade changes.
         A.  Storefronts. The following regulations apply to      3.  Changes can be accommodated by terraced
            storefront facades along sloping streets:                 planters and retaining walls. Retaining walls shall

           1.  Grade transitions on the building along the            not exceed 30 inches in height except along a
                                                                      maximum 15-foot section of frontage.
               sidewalk should be designed to maximize active
               pedestrian-scale frontages between waist and       4.  When the elevation of the first floor is more than
               eye level while minimizing blank walls.                3 feet above grade, windows should be provided
           2.  The interior floor level shall step to match           into the basement or lower floor elevations
               the exterior grade within 3 feet. With type 2
               design exception, changes in grade may be
               accommodated by a storefront window display
               space.
           3.  Knee wall and retaining walls shall not exceed 30
               inches in height except along a maximum 15 foot
               section of facade length.
           4.  If grade change is more than 9 feet along a
               single block face, entrance requirements may be
               increased to one entrance per 90 feet of building
               frontage.
           5.  If grade change is more than 9 feet along a single
               block face, building entrances adjacent to the
               street shall be within 3 feet of the elevation of
               the adjacent sidewalk.


                                    Arcade Opening
                                                   Shadow line


                                                   Recessed or
                                                   Interior Face
         Base




                                        Column
                sidewalk                Width


          Figure 2.3-L.  Example of Arcade.                     Figure 2.3-K.  Examples of Ground Story along Slope.


         135-2-10                                                                         DRAFT AuGuST 3, 2017